Inhibit is a DALI command supported by some DALI emergency products that invokes the Inhibit functionality described in IEC 60598.2.22 and its national derivations.
Inhibit functionality is a means to prevent an emergency device from entering emergency mode (running off batteries) for the 15 minute period following receipt of the command.
Inhibit mode can be cancelled by the reset inhibit command, a 15 minute period with no subsequent inhibit command or cycling of mains power.
The INHIBIT command times out after 15 minutes for safety but can be extended by resending the command.
Comments
0 comments
Article is closed for comments.