Configuration
The zc-iot-pwm can be configured in the following ways
- Using the zencontrol connect app to connect to the device directly
- Using the zencontrol cloud interface
- Using a third-party interface that has included support.
Below is an overview of how a third party can access the zc-iot-pwm settings.
Bus Unit Configuration
The zc-iot-pwm family has bus unit configurations to change the functionality of the outputs. To learn how to set Bus Unit Configuration, please see What is the Bus Unit Configuration?
The zc-iot-pwm family support three modes of operation which allow the device to operate as either 4 x DT6 LED drivers, 2 x DT8 TC LED drivers or 1x DT8 RGBW LED driver
Modes
|
Mode |
Name |
Description |
Output Address Map |
DALI ECG Addresses |
|||
| 1 | 2 | 3* | 4* | ||||
| 192 | DT6 Mode | All outputs are individual ECGs. | 1 | 2 | 3 | 4 | 4 |
| 193 | Tc Mode | 2 consecutive outputs are conjoined as ECGs supporting the TC colour type. |
1 |
1 |
2 |
2 |
2 |
| 194 | RGBW Mode** | All outputs are linked as a single ECG supporting the RGBWAF colour type. |
1 |
1 |
1 |
1 |
1 |
| 195 | Single DT6 | Output 1 as a DT6 device, outputs 2-4 mimic output 1 | 1 | 1 | 1 | 1 | 1 |
| 196 | Single TC | Output 1/2 as a single TC device, outputs 3/4 mimic 1/2 |
1 |
1 |
1 |
1 |
1 |
|
* Output count depends on physical number of outputs ** Not supported on 2 channel products |
|||||||