Overview
The zc-smart-blind has 3 ECG operating modes that change the functionality of the product.
ECG Operating Modes
Operating modes can be set as documented in the standard IEC 62386-102
| Mode | Name | Description |
| 0 | Compliance | Dali Compliance mode. (uses smart calibration) |
| 128 | Smart Calibration | The product will dynamically calibrate its range based on the runtime of the output. In this mode the device represents as a IEC 62386-208 standard device. More information can be found here. |
| 129 | Fixed Calibration | The product operates over a fixed period. In this mode the device represents as a IEC 62386-208 standard device. More information can be found here. |
| 130 | Dali 207 (DT6) Smart Calibration Mode |
The product operates over a fixed period. The product will represent as a IEC 62386-207 standard device. Due to the nature of a blinds motion and the calculations of a logarithmic dimming curve, this product always operates in a linear dimming curve to provide the best step size possible. More information can be found here. |
| 131 | Dali 207 (DT6) Fixed Calibration Mode |
The product will dynamically calibrate its range based on the runtime of the output. In this mode the device represents as a IEC 62386-207 standard device. Due to the nature of a blinds motion and the calculations of a logarithmic dimming curve, this product always operates in a linear dimming curve to provide the best step size possible. More information can be found here. |