The status of each exit and emergency devices can be seen through the status indicator. The single, 2 colour LED indicator displays whether testing was successful, currently undergoing, or awaiting the next test in compliance with AS/NZS2293.
Indicator | Description |
Green illuminated | Device is in normal mode |
Green slow flash | Test switch button has been pressed/held for any amount of time, and is not in any self tests |
Green 1x flash | A duration test is pending, the device is not in any self test but set to normal mode |
Green 2x flash | Lamp failure |
Green 3x flash | Battery failure |
Green 4x flash | Interface failure, DALI/Wi-Fi failure - had a short address and no longer set or had Wi-Fi and now not present. |
Green 5x flash | No DALI address/Non commissioned Wi-Fi/Can not connect to supplied Wi-Fi access point. |
Green 7x flash | Device performing function test. The test was triggered by a DALI command or function test interval. |
Green 9x flash | Device either doesn't support maintained mode or doesn't support the selected duration setting |
Yellow illuminated | Device is in normal mode |
Yellow 0.5sec On / 0.5sec Off | Last duration test failed, failed to meet duration. The device is not currently running a new test. Mains is on. |
Yellow 2sec On / 2sec Off | Device is performing a duration test |
Yellow 4sec On / 1sec Off | Last duration test passed, the duration was meet when last run. Test ran less than five days ago |
Yellow 4sec On / 1sec Off Green 1x Fast Flash |
Configuration menu entered |
Comments
0 comments
Article is closed for comments.