Operating Modes
ECD
Operating mode 0 is not normally recommended for use, this operating mode disables Standalone Mode functionality.
On products with SA1 and SA2, all operating modes are available.
On products which don't support SA2, only operating modes 0, 128, 129 are available.
On products which don't support SA1 or SA2, only operating modes 0, 128 are available.
Operating Modes | Function |
0 |
Standard SA1: Push Button SA2: Push Button |
128 |
Default SA1: Push Button SA2: Push Button |
129 |
SA1: Absolute Input SA2: Push Button |
130 |
SA1: Push Button SA2: Absolute Input |
131 |
SA1: Absolute Input SA2: Absolute Input |
ECG
It is recommended to leave ECG Operating mode at 128. Operating mode 0 will make Standalone Mode functionality only affect itself, not broadcast on the DALI line.
Operating Modes | Function |
0 | Standard |
128 | Default |
Configuring Operating Modes
Operating modes can be changed via several methods, outlined below.
Cloud
ECG operating mode can be changed from the Device types tab.
ECD operating mode can be changed from the Instance types tab.
Android Application
Both the zencontrol and Express apps allow ECD and ECG operating modes to be changed.
DALI Commands
For the following commands:
* Y is the HEX value of the operating mode desired
** SET OPERATING MODE must be sent twice within 100ms, without any commands in the middle.
ECD
Query:
QUERY OPERATING MODE (0xFFFE3E)
Set:
DTR0 Y* (0xC130YY)
SET OPERATING MODE** (0xFFFE18)
ECG
Query:
QUERY OPERATING MODE (0xFF9E)
Set:
DTR0 Y* (0xA3YY)
SET OPERATING MODE** (0xFF23)